The nameplate on a motor indicates that the motor has an flc of 15a and a service factor (sf) of 1.15. how much additional current can this motor safely handle for intermittent power demands?

Respuesta :

The additional current that this motor can safely handle for intermittent power demands is = 2.25A

What is Current?

Current is defined as the movement of electrons along a wire that produces electricity that is measured in Amperes (A).

A motor that has a service factor of 1.15 means that it can hold overload current of 15% more.

But 15% of 15A = 15/100 * 15

= 225/100

= 2.25A.

Therefore, the additional current that this motor can safely handle for intermittent power demands is = 2.25A